We use [[http://www.networkupstools.org/|NUT]]. We are monitoring our UPS through the serial port on [[Infrastructure/Gallium.club.cc.cmu.edu|gallium]]. We also run upsmon on the machines that are plugged into the UPS. We use [[http://www.networkupstools.org/|NUT]]. We also try to run upsmon on the machines that are plugged into the UPS.
Line 6: Line 6:

== Topology ==

 * gallium <-> Rack 0 UPS; APC Smart UPS 2200 XL
  * ?
 * argon <-> Rack 7 UPS; IBM RV 3000
  * osmium
  * vanadium
  * ytterbium
  * terbium

We use NUT. We also try to run upsmon on the machines that are plugged into the UPS.

Configuration

The NUT configuration files live in /etc/nut.

Topology

  • gallium <-> Rack 0 UPS; APC Smart UPS 2200 XL

    • ?
  • argon <-> Rack 7 UPS; IBM RV 3000

    • osmium
    • vanadium
    • ytterbium
    • terbium

On gallium

  • ups.conf - specifies the UPS name (upsium), driver (apcsmart), and serial port (/dev/ttyS1)
  • upsd.conf - specifies access controls to upsd, the main NUT daemon; only allow club hosts to monitor the UPS
  • upsd.users - user names, passwords, and privileges for access to upsd
  • upsmon.conf - specifies that gallium is the master for monitoring; gives information so upsmon can connect to upsd

In /etc/default/nut, specify START_UPSD=yes and START_UPSMON=yes.

Also one important thing to remember, is that you need a nut user. If you forget, you get the helpful error message "getpwnam(nut): Success" (at least in the sarge version).

nut:x:50:104::/var/lib/nut:/bin/false

On others

  • upsmon.conf - specifies that the upsd on gallium should be monitored; gives information so upsmon can connect to the upsd on gallium

In /etc/default/nut, specify START_UPSMON=yes.

How It Handles Issues

TODO: kbare - verify this is true.

When the battery level of the UPS becomes critical, the upsmon processes will notice, and initiate a system shutdown. The master will wait for all of the slaves to shut down, and then it will shut itsefl down, and power off the UPS.